Rules / always-false-condition
An alarm can never trip: the condition is always false after substitution
Once the assignments made in the same scan are substituted, the condition becomes NOT X AND X, which is FALSE for any X. Typically one program derives a command from a sensor while another checks "command present, sensor absent".
Severity: Critical
Rule id: always-false-condition
Condition can never be true
What the rule checks
A condition that becomes identically false (or identically true) once same-scan assignments are substituted. The classic shape: one program derives a command from a sensor, another checks the alarm “command present but sensor absent”, and substitution turns it into NOT X AND X, i.e. FALSE for any X. The alarm physically cannot fire: it is listed in the log, but there is no protection. The eye does not catch it because the assignment and the check live in different POUs, with the PLC_PRG call order between them. The rule substitutes only what is known for certain within the scan: the assignment must cover every execution path, and the source program must be called earlier. If a variable is assigned in several branches, every value is substituted and the rule fires only when the result is constant for all of them.
What it does to the plant
The alarm has a line in the log but no protection behind it: it physically cannot trip.
Example
VAR_GLOBAL xPressureOk : BOOL; xRunMakeup : BOOL; alarm_pressure : BOOL;END_VARPROGRAM PLC_PRGMakeup();Alarms();PROGRAM Makeupgvl.xRunMakeup := gvl.xPressureOk;PROGRAM AlarmsVAR tmrPressure : TON;END_VARtmrPressure(IN := NOT gvl.xPressureOk AND gvl.xRunMakeup, PT := T#5S);gvl.alarm_pressure := tmrPressure.Q;
VAR_GLOBAL xPressureOk : BOOL; xMakeupDemand : BOOL; xRunMakeup : BOOL; alarm_pressure : BOOL;END_VARPROGRAM PLC_PRGMakeup();Alarms();PROGRAM Makeupgvl.xRunMakeup := gvl.xMakeupDemand;PROGRAM AlarmsVAR tmrPressure : TON;END_VARtmrPressure(IN := NOT gvl.xPressureOk AND gvl.xRunMakeup, PT := T#5S);gvl.alarm_pressure := tmrPressure.Q;
Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.
How to fix
- Take the command from a source other than the signal being checked: the alarm “command present, sensor absent” only works when the command does not contain that sensor as a factor.
- Check the intermediate variable as well, not just the final expression: the same defect came back a second time in the same place through a one-line edit of the source.