Rules / cfc-div-zero

Division by zero in CFC: a literal 0 wired into DIV

In a CFC or FBD chart the divisor of a DIV or MOD block is wired to the constant 0. Executing the block raises an exception. It is usually a placeholder left over from debugging.

Severity: Critical Rule id: cfc-div-zero CFC: division by a literal zero

What the rule checks

In graphical code (CFC/FBD) the divisor of a DIV/MOD block is wired to a literal constant 0, which is a runtime exception when the block executes. Checked against the connection graph.

What it does to the plant

The task stops on an exception the first time the block executes.

Example

Bad: the rule fires
<pou name="FlowCfc" pouType="program">  <interface>    <localVars>      <variable name="rVolume"><type><REAL/></type></variable>      <variable name="rFlow"><type><REAL/></type></variable>    </localVars>  </interface>  <body><addData><data name="cfc" handleUnknown="implementation"><CFC>    <inVariable localId="1"><expression>rVolume</expression><connectionPointOut/></inVariable>    <inVariable localId="2"><expression>0</expression><connectionPointOut/></inVariable>    <block localId="3" typeName="DIV" executionOrderId="0">      <inputVariables>        <variable formalParameter="In1"><connectionPointIn><connection refLocalId="1"/></connectionPointIn></variable>        <variable formalParameter="In2"><connectionPointIn><connection refLocalId="2"/></connectionPointIn></variable>      </inputVariables>      <outputVariables><variable formalParameter="Out1"><connectionPointOut/></variable></outputVariables>    </block>    <outVariable localId="4"><expression>rFlow</expression><connectionPointIn><connection refLocalId="3"/></connectionPointIn></outVariable>  </CFC></data></addData></body></pou>
Fixed: the rule is silent
<pou name="FlowCfc" pouType="program">  <interface>    <localVars>      <variable name="rVolume"><type><REAL/></type></variable>      <variable name="rFlow"><type><REAL/></type></variable>    </localVars>  </interface>  <body><addData><data name="cfc" handleUnknown="implementation"><CFC>    <inVariable localId="1"><expression>rVolume</expression><connectionPointOut/></inVariable>    <inVariable localId="2"><expression>3600.0</expression><connectionPointOut/></inVariable>    <block localId="3" typeName="DIV" executionOrderId="0">      <inputVariables>        <variable formalParameter="In1"><connectionPointIn><connection refLocalId="1"/></connectionPointIn></variable>        <variable formalParameter="In2"><connectionPointIn><connection refLocalId="2"/></connectionPointIn></variable>      </inputVariables>      <outputVariables><variable formalParameter="Out1"><connectionPointOut/></variable></outputVariables>    </block>    <outVariable localId="4"><expression>rFlow</expression><connectionPointIn><connection refLocalId="3"/></connectionPointIn></outVariable>  </CFC></data></addData></body></pou>

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Wire a variable/setpoint into the divisor input instead of the literal 0; it is usually a debug stub left behind.
  2. If the divisor can go to zero at runtime, pick a safe value before DIV/MOD (a SEL on a compare-with-0).
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.

Local version on GitHub →

The same linter without uploading a file: command line and GitHub Action.