free quality report for PLCopenXML exports

Rules / copy-paste

Copy-pasted logic in a PLC program: why duplication is risky

Structurally identical blocks (even with renamed tags) mean every fix must be applied to each copy, and one copy usually gets missed. A shared FUNCTION_BLOCK with parameters removes the duplication.

Severity: Minor Rule id: copy-paste Duplicated logic block (copy-paste)

What the rule checks

Structurally identical blocks (even with renamed tags) are a source of bugs: a fix in one place is forgotten in the others, and copy-pasting someone else's loop drags along its gating flags. A candidate for a shared parameterised FB.

What it does to the plant

A defect is fixed in one loop and stays in the next one; a copied loop also drags along the interlock flags of the original.

Example

Bad: the rule fires
PROGRAM PumpsVAR    xRun1, xRun2, xFault1, xFault2, xOut1, xOut2 : BOOL;    rP1, rP2, rSp1, rSp2 : REAL;    xLow1, xLow2 : BOOL;END_VARIF xRun1 AND NOT xFault1 THEN    xOut1 := TRUE;    IF rP1 < rSp1 THEN        xLow1 := TRUE;    ELSE        xLow1 := FALSE;    END_IFELSE    xOut1 := FALSE;END_IFIF xRun2 AND NOT xFault2 THEN    xOut2 := TRUE;    IF rP2 < rSp2 THEN        xLow2 := TRUE;    ELSE        xLow2 := FALSE;    END_IFELSE    xOut2 := FALSE;END_IF
Fixed: the rule is silent
FUNCTION_BLOCK FB_PumpVAR_INPUT    xRun, xFault : BOOL;    rP, rSp : REAL;END_VARVAR_OUTPUT    xOut, xLow : BOOL;END_VARxOut := xRun AND NOT xFault;xLow := xOut AND rP < rSp;PROGRAM PumpsVAR    fbPump1, fbPump2 : FB_Pump;    xRun1, xRun2, xFault1, xFault2 : BOOL;    rP1, rP2, rSp1, rSp2 : REAL;END_VARfbPump1(xRun := xRun1, xFault := xFault1, rP := rP1, rSp := rSp1);fbPump2(xRun := xRun2, xFault := xFault2, rP := rP2, rSp := rSp2);

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Create one FUNCTION_BLOCK with input parameters (setpoints, loop tags) and instantiate it per loop.
  2. For per-channel repeats, use a FOR loop over an array of structures.
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.

Local version on GitHub →

The same linter without uploading a file: command line and GitHub Action.

Related rules

2026-11-26

Processing happens in memory, and the uploaded code is not stored. The tool advises; code changes are up to the engineer (see what the linter can't see). What happens to your code → · Rule reference · Your code & privacy · Industry benchmark · Feedback · GitHub