free quality report for PLCopenXML exports

Rules / for-unsigned-minus-one

FOR i := 0 TO n - 1 with an unsigned n: a 65535-iteration loop

If n is a WORD or UINT equal to zero, n - 1 wraps through zero to the type maximum. A loop that should not run at all runs tens of thousands of times in one scan.

Severity: Warning Rule id: for-unsigned-minus-one Loop up to X - 1 with an unsigned X

What the rule checks

The upper bound X - 1 with an unsigned X (UINT, WORD, UDINT, DWORD and the like) is never negative: with X = 0 the subtraction wraps around and yields the type's maximum, 65535 for a WORD. A loop that should not run at all runs tens of thousands of times per scan: the cycle time blows past the watchdog, and if the counter indexes an array, reads and writes go far beyond its bounds (without CheckBounds that corrupts neighbouring memory). The rule stays silent if X is a constant or the project somewhere checks X > 0, X >= 1, X <> 0, X = 0 or clamps X := MAX(…)/LIMIT(…). Most often X is a unit count entered on the HMI: during commissioning or after replacing the controller, zero is its most likely value.

What it does to the plant

The cycle time blows past the watchdog, and the index runs far beyond the array, corrupting memory.

Example

Bad: the rule fires
VAR_GLOBAL    wUnits : WORD;    aUnitFault : ARRAY[0..15] OF BOOL;END_VARPROGRAM ScanUnitsVAR    i : WORD;    xAnyFault : BOOL;END_VARxAnyFault := FALSE;FOR i := 0 TO gvl.wUnits - 1 DO    xAnyFault := xAnyFault OR gvl.aUnitFault[i];END_FOR
Fixed: the rule is silent
VAR_GLOBAL    wUnits : WORD;    aUnitFault : ARRAY[0..15] OF BOOL;END_VARPROGRAM ScanUnitsVAR    i : WORD;    xAnyFault : BOOL;END_VARxAnyFault := FALSE;IF gvl.wUnits > 0 THEN    FOR i := 0 TO gvl.wUnits - 1 DO        xAnyFault := xAnyFault OR gvl.aUnitFault[i];    END_FOREND_IF

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Wrap the loop in IF X > 0 THEN … END_IF or clamp the value where it is entered: X := LIMIT(1, X, N_MAX);.
  2. If X indexes an array, check the upper end too: X - 1 must not exceed the array's declared bound.
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.

Local version on GitHub →

The same linter without uploading a file: command line and GitHub Action.

Related rules

In-depth article

2026-11-26

Processing happens in memory, and the uploaded code is not stored. The tool advises; code changes are up to the engineer (see what the linter can't see). What happens to your code → · Rule reference · Your code & privacy · Industry benchmark · Feedback · GitHub