A POU without a single comment: the minimum PLC code needs

The rule flags a POU with substantial logic and no comment at all. The minimum is a header with the block's purpose and notes on setpoints, protections and anything non-obvious.

Severity: Minor Rule id: missing-comments POU without a single comment

What the rule checks

A POU with substantial logic and not a single comment is a nightmare when troubleshooting six months later. At least a purpose header and notes on the non-obvious parts.

What it does to the plant

A commissioning engineer cannot see the intent and "fixes" something that was working correctly.

Example

Bad: the rule fires
PROGRAM BoilerVAR    xRun : BOOL;    xFlame : BOOL;    xFault : BOOL;    rTemp : REAL;    rSet : REAL;    xBurner : BOOL;    xPump : BOOL;END_VARxPump := xRun;IF xRun AND NOT xFault THEN    IF rTemp < rSet - 2.0 THEN        xBurner := TRUE;    ELSIF rTemp > rSet + 2.0 THEN        xBurner := FALSE;    END_IFELSE    xBurner := FALSE;END_IFIF xBurner AND NOT xFlame THEN    xFault := TRUE;END_IFIF NOT xRun THEN    xFault := FALSE;END_IF
Fixed: the rule is silent
PROGRAM BoilerVAR    xRun : BOOL;    xFlame : BOOL;    xFault : BOOL;    rTemp : REAL;    rSet : REAL;    xBurner : BOOL;    xPump : BOOL;END_VAR// Boiler: two-position control with a 2 degC band, flame loss trips the burnerxPump := xRun;IF xRun AND NOT xFault THEN    IF rTemp < rSet - 2.0 THEN        xBurner := TRUE;    ELSIF rTemp > rSet + 2.0 THEN        xBurner := FALSE;    END_IFELSE    xBurner := FALSE;END_IF// burner on but no flame: latch the fault until the boiler is stoppedIF xBurner AND NOT xFlame THEN    xFault := TRUE;END_IFIF NOT xRun THEN    xFault := FALSE;END_IF

Both listings are run through the linter by an automated test: the rule fires on the first and stays silent on the second.

How to fix

  1. Add a POU purpose header and comments on setpoints/guards and non-obvious parts.
Check your project

Upload a PLCopen XML or CODESYS .export file: the report is free and the code is not stored.

Local version on GitHub →

The same linter without uploading a file: command line and GitHub Action.

Related rules

2026-11-26

Processing happens in memory, and the uploaded code is not stored. The tool advises; code changes are up to the engineer (see what the linter can't see). What happens to your code → · Rule reference · Your code & privacy · Industry benchmark · Feedback · GitHub